Section 1.3.7.1.4. Depot Level Inspectable Category
The capability of inspection in the field is generally less
than at the depot. The sizes of damage
assumed to exist following inspection are specified in Table 1.3.2. For this example, assume that penetrant or
ultrasonics will be used at the depot both exterior and interior to the lower
surface. If this type of inspection is
conducted, the damage likely to be found will be much smaller than the failed
skin panel. From Table 1.3.3, the
minimum damage size to be assumed at the hole is a through crack of 0.25 inch
uncovered length. The locations of the
0.25 inch flaw in both the skin and the splicing stringer should be selected on
the basis of inspectability but should be the location most critical to
subsequent growth. Assume for purposes
of illustration, that the damage is as indicated in Figure
1.3.14. The 0.005 inch flaw away
from the primary damage site represents the initial manufacturing type damage
as explained in Section 1.3.4.
Figure 1.3.14. Illustration of Primary Damage Following a
Depot-Level Penetrant or Ultrasonic Inspection
Residual
Strength Load, Pxx
The required level of residual strength Pxx for the depot or base level inspection category is PDM, as shown in Table 1.3.4. This is the maximum load that would occur in
the planned ¼ lifetime (10,000 hour) inspection interval. The method for establishing this particular
load level follows the method outlined in Example 1.3.3 where the one life time
exceedance curve is multiplied by a factor of 5 rather than 20.
Analysis
Guidelines
Figure 1.3.15 illustrates the slow
crack growth and residual strength guidelines for this category, as established
by JSSG-2006 paragraph A3.12.2. This
figure specifically shows that the post-inspection damage is restricted from
growing a crack to critical size and thereby causing failure of the structure
due to the application of PDM
in two times the inspection interval (½ lifetime, 20,000 flight hours).
Figure
1.3.15. Illustration of
Damage-Growth and Residual Strength Guidelines for Example Problem Qualified as
Depot-Level-Inspectable